Detector
Product Details
system specifications
| Model name | VLW (IFT-P) |
|---|---|
| Type | Normal
type, reuse type, air suction type, analog type, number of
air suction inputs 2, maximum air pipe distance 200m, Maximum use distance per number of air suction input 100m |
| Type
approval number | Gam11-14 |
| KC
certification number | R-R-CoC-IFT-P |
Nominal
sensing concentration range | 1 ~ 4%/m |
| Rated
voltage | DC 24V |
| Ambient
temperature/Relative humidity | 0°C ~ 39°C / 0 ~ 95% |
| Current
consumption | Monitoring 500mA / Alarm 1.2A |
| Sensing
method | A method of
measuring the value of light scattering in the laser chamber by sucking smoke
particles through the air suction pipe |
| Sensitivity
range | 0.001 ~ 20% obs/m |
| Color | Gray |
| Size | 254(W) X 180(H) X 165(D)mm |
| IP class | 65 |
| Weight | 4.0kg |