Automatic fire detection equipment
Product Details
system specifications
| Model name | FCM-1 |
|---|---|
| Type | Control repeater |
| Power used | 15 ~ 32 VDC |
| Operating temperature | 0°C ~ 49°C |
| Humidity | RH10%~93% non-condensing |
| Maximum current consumption | 6.5mA (LED on) |
| Maximum operating current | 485μA (LED Flashing) |
| Terminating resistance | 47KΩ |
| Size | 114(H) × 102(W) × 32(D) mm |
| Connectable device | phone, alarm, siren, time alarm |
| Features | Wiring monitoring function Automatic programming function High sensitivity noise removal function Easy address setting using decimal rotary method |
| Certification | UL, FM |